Product Safety
Last Updated: Feb 1st, 2008 - 10:12:17
|
See this article in our Digital Edition Download a pdf of this article (right click to save the pdf)
UL 1449 “Transient Voltage
Surge Suppressors” has been the safety standard for powerline surge
suppressors for over 20 years, but changes to the UL1449 standard have
opened the door to a viable alternative for surge suppression products.
UL 1449 has recently been significantly revised, and will be introduced
as a Third Edition and renamed “Surge Protective Devices.”
Manufacturers will be required to be in compliance with the changes by
October 2009. The focus of UL 1449 Third Edition has been on assuring
the safety of products which principally used fixed clamping components
such as MOVs (metal oxide varistors) and SADs (silicon avalanche
diodes) as their primary surge suppression component.
Since the safety testing assumes that products operate in a shunt mode
and have a fixed voltage clamping element, filters which operate in a
series mode and do not contain fixed voltage clamping elements, but
were previously UL 1449 Listed, would be subjected to tests that are
not relevant to determining the safety of the electromagnetic
interference filter technology.
As a direct result of many of the new shunt-mode safety tests being
directed principally toward fixed clamping component technology,
products which suppress surges and noise but use only electromagnetic
interference filter technology have necessarily moved away from UL
1449. These products are now certified under UL 1283, since the UL 1449
safety testing is no longer relevant to the electromagnetic
interference filter technology, even though a principal function of an
electromagnetic interference filter may be to filter off undesirable
noise and remove the damaging high frequency surge energy.
The Importance of Surge Suppression
A moment of reflection will show that powerline surges are nothing more
than a short burst of high frequency energy, with the dangerous surge
frequencies orders of magnitude higher in frequency than the 60 Hz
power frequency. Therefore, a well-designed electromagnetic
interference filter should be able to remove powerline surges by
filtering off the high frequency energy, noting the large frequency
separation. Electromagnetic interference filter designs become much
simpler for a given desired rejection as the frequency separation
increases. Of course, the powerline is a low impedance, high energy
environment, which puts special requirements on the design components.
While a basic electromagnetic interference filter can dramatically
reduce the surge voltage, modern computing systems have become
increasingly sensitive, and are being used in increasingly important
applications. For example:
- With
so much electronic equipment in operation, it is hard to determine
exactly how much surge suppression is required to assure optimum
protection of the various systems;
- Every system is no better than the weakest link;
- We
know that, if the worst-case surge can be suppressed to a level at or
below the power wave peak voltage, down-stream equipment will be
unaware a surge event occurred, so even the most susceptible products
will be protected;
- If surge voltage let-through can be dramatically reduced, there will be no degradation, no disruption, and no damage.
With these issues in mind, the total elimination of dangerous surge
energy even with the worst-case surges becomes an important design
goal.
Filtering to Achieve Total Surge Cancellation
Since a good electromagnetic interference filter should be able to
remove surge energy from the powerline, we undertook to develop a
different approach to surge suppression. To assure ourselves we were
addressing the worst-case situation, we first consulted IEEE/ANSI
C62.41. C62.41 describes locations within a building and anticipated
surge dangers at those locations. Although many UL 1449 products have
been characterized as protection for IEEE/ANSI Category A1 locations,
these locations are described as being 60 feet or more from the service
entrance. We wanted an electromagnetic interference filter that could
be placed anywhere within a building, even close to a branch service
panel or the main service entrance wiring.
According to C62.41, worst-case surges inside a building (IEEE/ANSI
Category B3 locations) could be a pulse as large as 6,000 volts peak,
3,000 amps peak with a half amplitude duration of 50 microseconds. An
electromagnetic interference filter designed for this Category B3
location would have to reduce this 6,000 volt pulse to less than 170
volts peak to pull it within the normal dynamic range of 120 Vac power.
This level of performance would qualify the electromagnetic
interference filter to be used anywhere within the building. A low pass
electromagnetic interference filter with 32 dB attenuation could
accomplish this task.
Since it is desirable to minimize the electromagnetic interference
filter “standby” current, the bulk of the filtering is put within a
full wave bridge, which offers several advantages. First, it allows the
use of large value electrolytic capacitors, needed to operate at the
low impedances required. Second, it also peak rectifies on the power
wave, and therefore the bulk of the filtering occurs for voltages
(surges and noise) that exceed the power wave peak voltage, without
adding significant “standby” current flowing from the normal 60 Hz
power (which would otherwise be characteristic of a low impedance
filter).
After several months of reviewing various electromagnetic interference
filter configurations and parameters for optimum performance, a
“Eureka” moment came when we considered the following:
- Many
years ago, in the design of an integrated circuit filter, we used phase
cancellation to improve a low pass filter design. An anti-phase signal
was added to the main signal path to result in significant (20 db)
additional rejection of the undesired signals, leading to a
significantly more stable integrated circuit.
- Audio
cancellation using anti-phase paths for noise reduction is fairly
common today. Was it possible to apply the same principles to the power
line?
Computer Analysis to the Rescue
Computer analysis showed that the basic low pass filtering removed the
dangerous higher frequency components, but there was still a low
frequency pulse of about 150 volts above the power wave peak voltage.
The issue then became one of deriving a cancelling voltage. The input
inductor bears the brunt of the surge voltage and current. Could a
cancelling voltage be derived from the input inductor?
We found that, by optimizing the turns ratio, coupling, and damping,
the input inductor could be tapped and properly phased to provide a 150
volt cancelling phase voltage for the worst-case surge. Indeed, the
residual low frequency pulse could be cancelled to below the power wave
peak for even worst-case conditions.
Since computer simulations verified the complete design, we built a
sample unit. Optimizing the input inductor to meet the computer design
parameters was challenging, but the first samples were fine tuned to
perform even better than the computer simulations, since the computer
simulations used worst-case design parameters.
As a result, we’ve engineered what we believe is a different approach
to surge suppression, one that removes dangerous surge energy from the
downstream protected equipment using practical components. The approach
utilizes a low pass electromagnetic interference filter that first
filters off the higher surge frequencies. Then, the residual low
frequency components are cancelled using well-established phase
cancellation principles to provide total surge protection from even the
worst-case surge energy. The result is a UL 1283 Listed electromagnetic
interference filter that cancels out dangerous surge energy, while also
filtering annoying powerline noise.
How Total Surge Cancellation Works
Although the actual circuit is complex, a simplified schematic shown in
Figure 1 clearly illustrates the critical functions. (The tapped
inductor is shown as an autotransformer, as the function is easier to
understand with this configuration.) While functionally described
previously in this article, the schematic will clarify the signal flow,
as follows:
- A surge enters at point A;
- The
tapped cancelling winding immediately begins to develop a cancelling
voltage due to the surge current flow in the primary winding;
- The
incoming surge voltage is filtered and delayed by the winding primary
inductance and the capacitor. Some residual low frequency surge
components appear at point B, but are delayed in time due to the
filtering action of the input inductance and filter capacitance;
- The
canceling voltage from the tapped coil is added to the point B filtered
surge, with the resultant surge cancelled voltage sent to the output;
- Adding
the cancelling voltage to the delayed residual surge voltage prevents
even the residual surge voltage from exceeding the power wave peak
voltage, reducing the surge voltage let-through to zero. (See the
oscillograms later in this article for performance to worst-case
surges).
Figure 1
Since the electromagnetic interference filter uses non-sacrificial
filter capacitors and inductors, and no fixed clamping components, we
predict that this type of device should have a long service life.
Total Surge Cancellation: Oscillogram Responses at Two Surge Levels
Figures 2, 3 and 4 represent a series of oscillograms showing a brief
history of 120 volt AC power quality electromagnetic interference
filter surge protection responses for both a reference electromagnetic
interference filter (introduced in 2002) and the total surge
cancellation filter described in this article.
Figure 2: Baseline response to 4KV, 2KA surge
Figure 3: Total surge cancellation response to 4KV, 2KA surge
Figure 4: Total surge cancellation response to 6KV, 3KA surge
UL 1449 Second Edition uses a suppressed voltage rating (SVR), with a
minimum value of 330 volts established with a 500 ampere peak current
surge, for transient voltage surge suppressor performance
characterization.
UL 1449 Third Edition performance characterization will use a voltage
protection rating (VPR—also with a 330 volt minimum) established with a
3,000 peak ampere surge. Since UL 1449-3 assumes a fixed clamping
element(s), the power wave peak voltage may be as high as 132 volts rms
or 187 volts peak (multiply the rms value by 1.414 to determine the
peak voltage--surges must be evaluated against the power wave peak
voltage). With allowances for component tolerances and the dynamic
impedance of the clamping components, a 330 volt lower limit as
specified in the standard makes technical sense for products using
fixed clamping voltage components.
To characterize the performance of a UL 1283 Listed surge suppressing
electromagnetic interference filter, we used a surge let-through
voltage. The surge let-through voltage is the surge voltage that
exceeds the powerline peak voltage. This measurement was used for this
technology since the electromagnetic interference filter technology is
dynamic, and the technology does not have a fixed voltage clamping
element. The actual suppression level “tracks” the incoming power wave
voltage, so the protection is optimized independent of the power line
voltage. Designs are available that operate from 85 vrms to 265 vrms.
This is possible since there are no fixed clamping voltage components
to limit the voltage range. However, the filter components must be
rated for the highest design voltage.
A 4,000 volt, 2,000 amp surge was applied to the baseline
electromagnetic interference filter product for reference. The two
horizontal dotted lines shown on each of the oscillograms represent the
normal peak positive and peak negative power wave voltage extremes. Any
significant surge voltage that exceeded the horizontal dotted lines
(surge voltage let-through) could harm down-stream products. At the
same time, if either the peak surge voltage let-through or its duration
was reduced, the protection would be improved. Likewise, if the surge
voltage was contained within the horizontal dotted lines, down stream
equipment would be unaffected.
Electromagnetic Interference Filter Surge Protection Performance
Figure 1 illustrates the performance of a reference electromagnetic
interference filter. This electromagnetic interference filter had a 100
volt surge voltage let-through pulse lasting only 17 microseconds, a
significant improvement in both peak voltage and duration over
conventional UL 1449 Listed technologies.
While the reference electromagnetic interference filter offered a
significant improvement over UL 1449 suppressors, the total surge
cancellation electromagnetic interference filters had less than a 10
volt surge voltage let-through lasting only 2 microseconds for
dangerous surge input levels. Oscillograms of voltage responses at
4,000 volts, 2,000 amps and 6,000 volts, 3,000 amps are shown in Figure
3 and Figure 4. In essence, all the surges applied to the total surge
cancellation electromagnetic interference filters were kept within the
normal 120 volt ac voltage variations, and any downstream equipment
would have been unaffected by any surge.
UL 1449 or UL 1283 Safety Listing?
Both UL 1449 and UL 1283 are safety standards. The safety testing in
both documents is similar where wire sizes, temperature rating of
components, allowable temperature rise, exposure to anticipated failure
modes, etc. are concerned. However, a principle difference between UL
1283 and UL 1449 occurs when tests are applied which evaluate clamping
components such as MOVs. These tests are very specific to the
components that are representative of the dominant technologies used in
the marketplace.
While UL 1449 Third Edition will be the prevailing standard for surge
protection devices, certain filters with a UL 1283 Listing may be more
effective at removing dangerous surge voltage from protected equipment.
The core technology behind some of these filters has a proven long-life
expectancy, and such devices can remove both the surge danger and
associated noise. Therefore, where vital or sensitive equipment needs
the best available protection from surges and noise, such total surge
cancellation electromagnetic interference filters may be a better
choice than the conventional UL 1449 Listed products. n
J. Rudy Harford is Chief Engineer at Zero Surge, and can be reached at rharford@zerosurge.com.
Note: The filter described in this article is protected by U.S.
Patents: 4,870,528, 4,870,534, 6,728,089, 7,068,487 and 7,184,252.
© 2007 Conformity